Deviation Register
Map/360 split with red deviation pins • Filterable table • Evidence & status history
Site Plan — Orthomosaic (14 Nov 2026)
360° View — Capture Point CP-12 (Digester D-2)
Deviation Register — Filterable Table
| ID | Element | Location / Grid | Type | Design vs Actual | Difference | Tolerance | Status | Owner | Evidence |
|---|---|---|---|---|---|---|---|---|---|
| D-01 | Digester-2 Raft Foundation | Grid B-3 / D-2 | Position | Design: 0,0 → Actual: +180mm E, +45mm N | 180 mm East | 50 mm | Open | Site Eng. - Kumar | |
| D-02 | Compressor Plinth C-201 | Grid E-7 / Comp. House | Dimension | Design: 3000mm × 2000mm → Actual: 2700mm × 2000mm | 300 mm Short | 25 mm | Open | Struct. Eng. - Patel | |
| D-03 | Pipe-Rack Pedestal P-7 | Grid C-5 / Pipe Rack | Missing | Design: Present → Actual: Not Found | — | N/A | NCR Raised | Piping Lead - Singh | |
| D-04 | Gas Holder Foundation Ring | Grid D-4 / Center | Position | Design: Center (0,0) → Actual: +220mm S, +80mm W | 234 mm SW | 75 mm | Under Review | Vendor - GAIL | |
| D-05 | Pipe-Rack Anchor Bolt Group | Grid B-5 / Pipe Rack | Position | Design: 200mm spacing → Actual: 185-215mm variance | Up to 15 mm | 10 mm | Closed | QC - Sharma | |
| D-06 | Control Room Building Corner | Grid A-1 / Admin | Dimension | Design: 12000mm × 8000mm → Actual: 12050mm × 8000mm | 50 mm Long | 25 mm | Under Review | Civil - Reddy | |
| D-07 | Flare Stack Foundation | Grid F-8 / Flare | Missing | Design: 4 anchor bolts → Actual: 2 bolts installed | 2 Missing | 0 | NCR Raised | Struct. - Iyer | |
| D-08 | Weighbridge Approach Slab | Gate / Entry | Dimension | Design: 200mm thick → Actual: 175mm avg | 25 mm Thin | 15 mm | Open | Vendor - ABC |
Showing 8 of 23 deviations (5 Open, 3 Under Review, 2 NCR, 1 Closed)